Diesel generators suddenly shut down during operation, which is generally caused by blocking or leakage of fuel supply systems.
cause of issue:
1. Diesel generator oil passage or oil filter is blocked.
2. Diesel generator diesel filter block plug.
3. There is air or various oil journals in the diesel generator oil path to loose, generating oil leakage.
4. Diesel generator air filter is partially blocking, resulting in less intake of diesel generators.
5. The diesel generator oil pump is faulty.
6. Diesel generator fuel injection pump card is dead in the position of no oil.
7. The fuel injection hole of the diesel generator injector or the needle valve card is in the position of the oil supply.
Troubleshooting method:
1. Remove the diesel generator high-pressure oil pump back oil screw, press the right hand to press the oil pump piezoelectric, and the amount of oil is in line with the requirements, but there are more impurities from the diesel flowing from the filter. Disassemble the filter, check whether the diesel filter is blocked, and the diesel filter has been discovered that the diesel filter has more, the diesel filter has been lost. Replace the new filter, the diesel generator is less than 5 min after starting.
2. Remove the diesel generator filter oil return screw, press the oil pump, and find that the oil pump is fine and sealed.
3. Remove the high pressure oil pump side cover, unscrew the fixed nut of 4 high-pressure tubes, use a flat screwdriver to shake the plunger, observe whether the cylinder is oil, check the plunger and oil valve, and the result is normal. Diesel generators should be difficult when the diesel generator combustion is difficult, and this diesel generator is easy to start, and it should not be a problem of air leakage, valve gap or oil supply advance angle.
4. Remove the oil pump, check the roller and rod of the oil pump, find that the rollers enters the top rod sleeve, the position of the two lock pieces is 90 °, the roller is killed, and it cannot be turned back and forth, resulting in the diesel generator start The post-oil pump cannot work.
5. Adjust the relative position of the two locking pieces, install the oil pump and the oil pipe screws, high pressure no tube with the high pressure oil pump. Start diesel generators, observe no stop after half an hour, the fault is excluded.
Diesel generators generally have two types: pressure lubrication and spatter lubrication. During the operation of the diesel generator, the oil pressure is too low or too high will affect the quality of the diesel engine. Therefore, the diesel generator must control the oil pressure within the specified range. The oil pressure of the 135 series non-pressure diesel engine is generally controlled at 0.25 to 0.35 MPa (2.5 ~ 3.5 kgf / cm2). The oil pressure of the booster diesel generator should be controlled at 0.35 ~ 0.45 MPa (3.5 ~ 4.5 kgf / cm2). ). No matter what model of diesel engine starts 1min, if the pointer to the oil pressure gauge is not changed, it should be quickly stopped. After identifying the cause and troubleshoot, start the diesel generator and observe the change of the engine oil pressure gauge.
Diesel generators From low-speed to rated speed, the oil pressure should be gradually increased. After the diesel engine reaches the rated speed, the oil pressure slowly returns to the specified value. If the oil pressure in 20 min cannot return to the specified value, the oil pressure is adjusted. 135 Series Diesel Engines have a regulator valve on the side of the oil filter, remove the nut, loosen the lock nut, rotate the adjustment bolt with a screwdriver. When the rotation is rotated, the oil pressure is raised; when the oil is rotated, the oil pressure is lowered. After adjusting, tighten the nut. It is necessary to make special reminders that if the rear oil pressure is still too low, the quality of the suction plate and the oil should be checked.
Jiangsu Xingguang Power Equipment Co., Ltd. has test equipment, advanced production technology, professional manufacturing technology, perfect quality management system, strong research and development technology strength, with 64 sales service department, ready to provide users with diesel generator set equipment installation , Debug, repair a dragon service.