Routine examination before the operation of diesel generator
Views: 0 Author: Site Editor Publish Time: 2015-04-12 Origin: Site
Routine examination before the diesel generator set: First, the appearance check: Whether the exterior of the generator set engine is damaged, complete, whether the screw is tightened, whether the generator output line and the control line are damaged. Second, the fuel system: 1. Is the amount of diesel oils, the wiring pipe has a phenomenon such as oil or pipeline, and excludes the remaining air in the fuel system. 2, lubrication system: Is the engine lubricant enough? The new engine and the renovated engine must implement the following maintenance after the initial operation of 50 hours: 1) Replace the engine lubricating oil. 2) Replace the engine oil filter. 3) Replace the engine diesel filter. 4) Check to adjust the valve gap. 5) Check the external screws of the engine. Third, the cooling system: Check if the amount of water of the cooling heat sink is sufficient, and a rust inhibitor is added. Fourth, battery: Check if the electrolyte of the battery is in normal liquid surface, whether the voltage is correct, and the joint is tight. 5. Can the generator set charger function properly? 6. Exhaust system: Whether the silencer is damaged and inspects the strength of the exhaust pipe installation. 7. Whether the environment around the generator set is clean and cleaned up the surrounding flammability and debris. Eight, the generator room ventilation must remain good. Nine, prohibiting idle people from entering the generator room.