How long does the customer call for 20KW generators to pay for a small load?
Views: 0 Author: Site Editor Publish Time: 2014-04-08 Origin: Site
Yesterday, users called, how long does the 20KW diesel generator group he purchased can long? The reason is that the generator is used in the gas station. Now there is now the electric machine to carry it up every time there is a user to refuel, it will be closed, and the user feels very troublesome. If you think, let the generator have been running, Small loads when you don't cheaper. In fact, small load is not operational, just generates a certain impact on the generator. At that time, the company's technical staff summed up:
Long-term small load is running, it will be easy to makegeneratorThe group appeared as follows: 1. Piston - Cylinder jacket seal problems, machine oil, enter the combustion chamber burning, exhaust and blue smoke; 2. If a booster diesel generator, due to small carrier load, low pressurization pressure. It is easy to cause the sealing effect of the supercharger oil seal (non-contact), and the oil is blown into the pressurized chamber, and the air is allowed to enter the cylinder; 3. Some oils from the top to the cylinder are involved in combustion. Some oils cannot completely burn, in the valve, intake, piston top, piston ring, etc., there is a part, and some are discharged with the exhaust. In this way, the cylinder sets will gradually accumulate oil in the airway, which will also form a carbon. 4. The supercharger indoor engine oil accumulates to a certain extent, it will leak from the combined surface of the supercharger; 5. The long-term small load operation of the generator set will lead to the wear of the power generator's moving parts, the deterioration of the engine combustion, etc., resulting in the advanced consequences of the overhaul period. After listening to the explanation, the user said that because the power outage is temporary, it may be a few hours, generally not more than half a day, then in this case,generatorThe impact will not be too large, and the user can use small load.