(1) AutomaticDiesel generator setsstatus
1. Keep the battery pack of the starter motor reaches the start voltage.
2, keep the heat sink cooling water level, the circulating water valve is often opened.
3, the crankcase oil level is maintained in the range of ± 2 cm in the amount of oil measurement.
4, the oil tank oil is more than half, the fuel oil supply valve is often open.
5. The \"Run-Stop-Auto \" switch of the generator set control screen is placed in the \"Auto \" location.
6, the mode switch of the unit distribution screen is in the \"Auto \" location.
7. The radiator fan switch is in the \"automatic \" location.
8. The unit is started after receiving the video of the mains, confirming the city's electrical pressure, cutting the converted cabinet city electric switch, closing the conversion cabinet power sag, starting the air supply and exhaust of the machine room.
(2) Manual startup
1. When the room temperature is below 20 ° C, the electric heater is opened and the machine is preheated.
2. Check the body and the surrounding debris, if it should be cleared in time.
3, check the crankcase oil level, fuel tank oil level, and heat sink. If the oil level water level is lower than the specified value, it should be added to the normal position.
4. Check if the fuel oil supply valve and the cooling water passage are in the open position.
5. Check whether the battery pack voltage of the starting electric electric battery is normal.
6. Test the test button of the power distribution screen, observe whether the alarm indicator is turned on and shines.
7. Check if the power distribution screen is placed in a hierarchy, and each meter indicates whether it is in zero.
8. Start the wind and exhaust air.
9. Press the start button of the engine to activate it. For example, Di fails, press the corresponding reset button on the power distribution screen, and the alert is eliminated, and the unit replys the normal state to make a second start. After startup, the machine runs normally, the cooling pump operation indicator lights and the road instrument indicates normal and successfully started.
(3) Manual operation parallel power supply
1. The oil temperature, water temperature and oil pressure of the generator set to be used in the merger, and the operation is normal.
2, the value of the output voltage and frequency of the pair generator set is consistent with the numerical value on the busbar.
3. Turn the synchronizer handle of the generator set to be used in the\"closing\" position.
4. Observe the indicator and pointer of the synchronization indicator.
5. Observe the indicator of the synchronous indicator, when fully extinguished, or rotate to zero, you can hit the cap switch.
6, the unit enters the pair of car, then rotates its synchronizer handle back to \"shutdown \" position.
7. If the synchronizer is closing, the synchronizer rotates too fast or in turn, it will not be allowed to be passed.
8. After the manual pair is successful, it should be immediately contacted with the low voltage distribution room, and the total distribution screen feed is implemented.
(4) Running safety management
1. Check the indicator instrument according to the specified time, pay attention to the pressure of the lubricant, and whether the water temperature changes. The pressure of the lubricant shall not be less than 150 kPa, and the cooling water temperature shall not be higher than 95 ° C.
2, check the crankcase oil level, fuel tank oil level, and heat sink, lower than normal positions should be supplemented.
3. Whether the distribution screens and the alarm indicator are normal. Any red light is on a fault, the green light is a normal running indicator.
4, check if the charger is charged normally.
5. Listening to the sound sound of each part of the machine is normal.
6. Handmark body housing, bearing portion housing, tubing, water pipe, and feel temperature.
7. Pay attention to whether the generator or electrical equipment has an odor.
8. It is found that there is a poor situation, and it should be resolved immediately; severe stop processing.
9. If the fault is stopped, the fault must be eliminated, and then the repeat of the dynamic group is repeated, the unit can be operated again.
10. For each running parameters, each class records are not less than twice.
(5) Parking
1. The output feed switch of the total control screen is separated by the power grid.
2, the diesel generator set is not stopped after 10 minutes.
3, stop the fan, cooling water pump, etc.